kVA to kW Calculator

Commercial and three-phase generators are often rated in kVA, while your loads are measured in kW. This calculator converts between them using power factor, so you can tell what a generator rating means for the equipment you need to run.

Electricity basics

kVA to kW Calculator

Convert between apparent power (kVA) and real power (kW) using power factor. Common on standby and commercial generator ratings.

kVA
kW
PF
Three-phase generators are usually rated at 0.8 PF; single-phase home units at 1.0.
CONVERSION
Result
—

kVA is the total power a generator's alternator must carry; kW is the useful power your loads consume.

Formulas

  • kW = kVA × power factor
  • kVA = kW ÷ power factor
  • Reactive power: kVAR = √(kVA² − kW²)

Example: a generator rated 25 kVA at 0.8 power factor delivers 25 × 0.8 = 20 kW of real power.

kVA, kW and power factor explained

  • kW (real power) is the power that does useful work, such as turning a motor, heating an element or lighting a lamp. It is what fuel is burned to produce.
  • kVA (apparent power) is volts × amps, the total the alternator and wiring have to carry.
  • Power factor is the ratio kW ÷ kVA. Motors and transformers draw some current that does no useful work, so their PF is below 1.

Industrial generator ratings conventionally assume a 0.8 power factor because mixed motor loads in commercial buildings typically fall around there. That is why a “100 kVA” generator is normally an 80 kW generator. Single-phase residential standby generators are usually rated directly in kW at a power factor of 1.0.

kVA to kW conversion table (PF 0.8)

kVAkW at 0.8 PFAmps at 208 V three-phaseAmps at 480 V three-phase
10827.812.0
252069.430.1
504013960.1
10080278120
150120416180
250200694301
5004001,388601

Amps = kVA × 1,000 ÷ (√3 × volts). Convert for other voltages with the watts to amps calculator.

Frequently asked questions

Which matters more when sizing a generator, kVA or kW?

Both. The engine must supply the kW, and the alternator must carry the kVA. If your loads have a power factor lower than the generator’s rated PF (for example a lot of motors at 0.7), the alternator can hit its kVA limit before the engine reaches its kW rating.

Is kVA the same as kW for home generators?

For practical purposes, yes. Residential single-phase generators are rated at a power factor of 1.0, so a 22 kW home standby unit is also 22 kVA. Household loads are mostly resistive or power-factor corrected.